SmartFan® Nimbus Manual

  • Mounting & Connections

  • MOUNTING

    Electrical "job box" mount (Fig 3)

    The Nimbus can be supplied in circuit board form or with a cover, ready to mount in a standard 4x4x1.5 electrical job box. When supplied in the job box form, part number 240_JW__ or 240_3W__, connections are made through 4.0” (10cm), 18AWG wires. Wires should be terminated using wire nuts (not included) according to local electrical codes. Unused wires may be cut off at the circuit board or can be depopulated at the factory for production orders. Caution: bundling unused wires together may cause a short and damage the unit.


    Circuit Board form

    When supplied in the circuit board form, a spacing of ¼” (6.3mm) should be maintained between the circuit board and chassis ground and 5/16” (8mm) to any uninsulated secondary circuits to satisfy safety agency requirements. To enable part numbers 240x6xxx or 240x7xxx to pass HI-POT testing, avoid making connection to ground at the mounting hole closest to the heatsink, H1. See Figure 4.


    DIN Rail Option (Fig 1)

    Units supplied in circuit board form may be mounted on a DIN rail using DIN rail kit CRI #DIN350.


    CONNECTIONS

    Power Connections

    It is recommended that an adequately sized circuit breaker be connected between the power service and the control to permit fail-safe removal of power before making adjustments or connections. Connect line power (white) to location N. Connect line power (black) to location L. When using an electrical “job box” mount version secure any ground (green) wire to a steel electrical box or consult local electrical codes.

    The Nimbus is not compatible with Uninterruptible Power Supplies (UPS) that generate a square wave.


    Fan Connections

    Connect fan or fans to positions marked F (red) and L (black). Any number of fans may be controlled in parallel from one unit as long as the total current does not exceed the current rating. See table 1 and figure 9.


    Temperature Sensor Selection and Connection

    The Nimbus will accept signals from up to 3 temperature sensors and control fan speed based on the hottest sensor. Choose an air, surface or liquid temperature sensor from the CRI catalog or website at www.controlres.com. Each sensor, S1, S2, S3 shares a common return marked SRTN. CAUTION: SRTN is a non-isolated input; use CRI sensor P11 or other sensor with a jacketed cable if installing temperature sensors in a dwelling. When fewer than 3 sensors are used, sensors may be hooked up to S1, S2 or S3. In “Temperature mode”, if no sensors are connected or all sensors read below -25°C, fans will run at full speed and the temperature alarm will activate. The Nimbus can also be supplied with a board mount sensor, contact customer service for details. See wiring diagram, figure 9.


    Remote Powered Transducer Connections

    When used in the remote transducer mode, the Nimbus can power and control from any 0-5VDC transducer (humidity, pressure, flow etc.) with a maximum supply current of 5mA. Connect the + lead to SRTN, connect – to S1, connect Vout to S2.

    Refer to “USING REMOTE POWERED TRANSDUCER MODE” section to set control parameters for your transducer.


    Current or Voltage Control Signal Connections

    When used in the current or voltage control mode (see table 2), connect a 0-10VDC or 0-20mA control signal to –ISO+ as shown in figure 9.

    SmartFan Nimbus Wiring Diagram
    Figure 9: Wiring Diagram
    Click on image for larger version


    Over Temperature and Loss of Signal Alarm Connection (for 240Bxxxx models only)

    When used in the temperature control mode, (see table 2) an over-temperature alarm can be triggered when the temperature goes 10˚C (18˚F) above the control temperature (TC) or below -25°C. When used in the Voltage or Current signal mode a “loss of signal” alarm can be triggered when DIP switch #6 is in the ON position. Alarm connections are made at –ALM+

    The alarm output is a normally open, optically isolated MOS Relay. When no alarm condition is present, the relay is closed and can conduct up to 100 ma. AC or DC, of load current. When the alarm is triggered, the relay opens, and can support up to 300 Volts AC or DC across its terminals. Other alarm trigger points can be supplied, contact customer service for details. See figure 9, 9a, 9b or 9c for possible alarm configurations.

    SmartFan Nimbus Wiring Diagram
    Figure 9a-d: Examples of Alternate Alarm and Control Input Configuration
    Click on image for larger version


    Table 11: Pin-out and Connection Options
    Pin-outs Connection Options
    Board Reference Description Terminal Block (T) 4" (100mm) Wire (W)
    F: TB1 (pin 1) Fan 14 - 24 AWG Screw Clamp 18 AWG Red
    L: TB1 Fan 18 AWG Black
    L: TB1 Line Power 18 AWG Black
    N: TB1 Line Power 18 AWG White
    SRTN-: TB2 (pin 1) Sensor (return) 18 AWG Brown
    S1: TB2 Sensor #1 18 AWG Orange
    S2: TB2 Sensor #2 18 AWG Orange
    S3: TB2 Sensor #3 18 AWG Orange
    -ALM: TB3 (pin 1) - Temp. Alarm 18 AWG Blue
    ALM+: TB3 + Temp. Alarm 18 AWG Yellow
    -ISO: TB3 - Control Signal 18 AWG Violet
    ISO+: TB3 + Control Signal 18 AWG Gray

    ADDITIONAL MANUAL PAGES

    Use the links below for addtional manual pages or for a complete manual (9 pages), click on the Operation/Installation Manual PDF link above.





    Control Resources Home | News and Info | Technical Data | Catalog | Contact Us | Applications | About Control Resources | Site Map
    Control Resources Incorporated 11 Beaver Brook Road Littleton MA, 01460 USA Tel: 978-486-4160 Fax: 978-486-4772 email: sales@controlres.com