Isolated Temperature Control Mode: Connection for the isolated temperature control mode is
made on the Isolated I/O terminals using the COM pin
for negative reference and POT pin for the temperature
control.
Set registers 40001 and 40017 to 1025 (0x0401) for
forward run isolated Temperature control mode.
Set register 40014 to desired ramp up rate (1Hz/Sec)
Set register 40015 to desired ramp down rate (1Hz/Sec)
Set register 40030 to 1 to save to EEPROM.
The Isolated Current Control mode is split into the
following three control modes:
- Positive Slope
- Negative Slope
- Two Speed
Positive Slope:
Set register 40019 to the maximum output that the motor
should receive (1Hz resolution) Point A
Set register 40020 to the minimum output that the motor
should receive (1Hz resolution) Point B
Set register 40025 to the temperature (-20-100°C) where
the maximum output will occur. Point E
Set register 40026 to the temperature (-20-100°C) where
the minimum output will occur. Point D
Set register 40027 to the temperature (-20-100°C) where
the alarm will occur. Refer to register 40013 for alarms
and configuration.
|
Negative Slope:
Set register 40019 to the maximum output that the motor
should receive (1Hz resolution) Point A
Set register 40020 to the minimum output that the motor
should receive (1Hz resolution) Point B
Set register 40025 to the temperature (-20-100°C) where
the maximum output will occur. Point D
Set register 40026 to the temperature (-20-100°C) where
the minimum output will occur. Point E
Set register 40027 to the temperature (-20-100°C) where
the alarm will occur. Refer to register 40013 for alarms
and configuration.
Two Speed:
Set register 40019 to the maximum output that the motor
should receive (1Hz resolution) Point A
Set register 40020 to the minimum output that the motor
should receive (1Hz resolution) Point B
Set register 40025 to the temperature (-20-100°C) where
the maximum output will occur. Point D
Set register 40026 to the same value as register 40025.
Set register 40027 to the temperature (-20-100°C) where
the alarm will occur. Refer to register 40013 for alarms
and configuration.
|