MOTOR COMPATIBILITY
For maximum motor life without using a line filter,
the use of an inverter duty motor is recommended.
CONTROL MODES
Default Control Mode: Stratus II is factory set to control
single phase fans from an analog voltage signal. The
drive will accept a 0-5VDC or 0-10VDC input signal and
control motor speed as shown in figure 1.
Fixed Speed Mode: In default control mode, Stratus II
can set motors to a fixed frequency using SW2. Set
switch 7 to ON and use Table 1 for frequency settings.
|
STOP on Contact Closure to GND: In default
control mode, Stratus II can turn motors off when a
contact closure is present at the Non-Isolated I/O
terminals, GND and Z. Refer to wiring diagram.
Reference level of this connection is at VBUS- and is
non-isolated Hi-Voltage. Consult factory before
installation.
Using Single-Phase or Three-Phase Motors:Stratus II
can control single or three-phase motors from a singlephase
power source.
To control a 1PH motor set SW2, #8 to the OFF position.
To control a 3PH motor set SW2, #8 to the ON position.
Power must be cycled before this setting will take effect.
Programmable Control Modes: Stratus II must
be programmed using a Modbus interface. If Modbus is
not available, special versions of Stratus II can be
programmed at the factory with the following control
modes:
- Isolated Voltage Control (05V / 010V)
- Isolated Current Control (420mA)
- Isolated Potentiometer Control (1K -100K )
- Isolated Temperature Control (CRI Thermistor)
- Isolated Modbus Control (J1)
- Non-Isolated Fixed Speed Switch Control (SW2)
- Non-Isolated Potentiometer Control (A/B)
- Non-Isolated Temperature Control (A/B)
- Non-Isolated Contact Closure Control (Z)
Isolated Voltage Control Signal Connections (default)
The Stratus II will accept a signal from a process sensor
producing an output of 0-5VDC or 0-10VDC. Connection
is made at the Isolated I/O terminals with no
programming required. Scaling and alarms can be
adjusted using Modbus. Refer to wiring diagram for
signal and alarm connections.
Isolated Current Control Signal Connections
The Stratus II will accept a signal from a process sensor
producing an output of 4-20mADC. Connection is made
at the Isolated I/O terminals. Configuration using
Modbus is required for processing a current signal. Refer
to wiring diagram for signal and alarm connections.
Isolated Potentiometer Control Signal Connections
The Stratus II will accept a signal from a 1K to 100K
potentiometer. Connection is made at the Isolated I/O
terminals. Configuration using Modbus is required for
processing a potentiometer signal. Refer to wiring
diagram for signal and alarm connections.
Isolated Temperature Sensor Selection and Connection
The Stratus II will accept a signal from a sensor and
control fan speed based on temperature. Connection is
made at the Isolated I/O terminals (Refer to wiring
diagram). Configuration using Modbus is required for
processing a temperature signal. When sensing air
temperature, use CRI sensor P10-F. For sensing
temperatures of liquids or surfaces, contact CRI
customer service.
Isolated Modbus Control (J1)
The Stratus II can be fully configured using Modbus RTU
protocol. See Modbus section for specifications.
Non-Isolated Fixed Speed Switch Control (SW2)
The Stratus II can control speed based on a fixed setting
of SW2. In default control mode, Stratus II can set
motors to a fixed frequency using SW2. Set switch 7 to
ON and use Table 1 for frequency settings.
Non-Isolated Potentiometer Control (A/B)
The Stratus II will accept a signal from a 1K to 100K
potentiometer using a non-isolated input. Connection is
made at the Non-Isolated I/O terminals. Configuration
using Modbus is required for processing this type of
potentiometer signal. Refer to wiring diagram for signal
and alarm connections. Reference level of this
connection is at VBUS- and is non-isolated Hi-Voltage.
Consult factory before installation.
Non-Isolated Temperature Control (A/B)
The Stratus II will accept a signal from a sensor and
control fan speed based on temperature. Connection is
made at the Non-Isolated I/O terminals (Refer to wiring
diagram). Configuration using Modbus is required for
processing a temperature signal. When sensing air
temperature, use CRI sensor P10-F. For sensing
temperatures of liquids or surfaces, contact CRI
customer service. Refer to wiring diagram for signal and
alarm connections. Reference level of this connection is
at VBUS- and is non-isolated Hi-Voltage. Consult factory
before installation.
Non-Isolated Contact Closure Control (Z)
The Stratus II can process a contact closure (Digital)
function as a STOP or programmable set point. See
Modbus section for Setup. Reference level of this
connection is at VBUS- and is non-isolated Hi-Voltage.
Consult factory before installation.
Alarm
The RELAY alarm output is a normally open, optically
isolated MOS Relay. When no alarm condition is
present, the relay is closed and can conduct up to
100mA, of load current. When the alarm is triggered, the
relay opens, and can support up to 300 Volts AC or DC
across its terminals. Alarm threshold can be configured
using Modbus. See Wiring Diagram for alarm
configurations.
|