SmartFan® Stratus II


MODBUS & DEFINITIONS


Stratus II Variable Frequency Drive AC Motor Speed Control

Isolated Modbus Control Mode: Using an RS-485 2-wire Modbus communications link, Stratus II can control motor speed, acceleration, deceleration and direction.

Modbus RTU Protocol
Baud Rate: Settable (default is 9600)
Word Length: 8
Parity: None
Stop Bits: 1
MODBUS ID: 1-63

Setup for Modbus Control:Use switch SW2 to select a unique ID number between 1 and 63 on your Modbus network. To set an ID number, turn #7 OFF and turn ON any number of switches 1-6 on SW2 and add up their associated “Value” see chart below. Example: turning ON “2, 4 and 6” would set the ID number by 2+8+32=42.

Connecting to a Modbus Network:Use an RS-485 2-wire twisted pair cable, connected to the Modbus network (refer to wiring diagram for proper pin out).

Register Definitions:

40001 – Run Control: Enter the desired control method. Only one control method may be selected at a time. Drive will use the 1st control bit set.

40002 – Target Frequency: Set the desired output frequency when in Modbus mode. In all other modes it is read only and displays target output frequency.

40003 – Target Speed: Set the desired output % when in Modbus mode. In all other modes it is read only and displays target output percentage.

40004 – Output Frequency: Displays the current output of the drive in Hertz.

40005 – Output Speed: Displays the current output of the drive in %.

40006 – Control value: Displays a representation of the analog control in % full or Temp °C.

40007 – Alarms: Displays all active alarms. See table 4.

40008 – Bus Voltage: Displays the DC bus voltage in Volts. (1V res)

40009 – Bus Current: Displays the DC bus current in Amps. (0.1A res)

40010 – Temperature: Displays the temperature of the inverter module in °C. (1°C res). 100°C shutdown.

40011 – Revision: Displays the firmware revision.

40012 – Modbus ID: Displays the Modbus ID.

40013 – Configuration: Used to configure specific control preferences.

40014 – Ramp Up Rate: Enter the desired increase in output frequency rate. (1Hz/sec res)

40015 – Ramp Down Rate: Enter the desired decrease in output frequency rate. (1Hz/sec res)

40016 – Current Limit: Enter the desired output current fault level (0-100) (.1A res). Any current beyond this setting will cause Stratus II to lock-up and set an alarm. Power must be cycled to clear the alarm.

40017 – Startup Run: Enter the configuration to be loaded into Register 40001(Run Control) at startup.

40018 – Startup Frequency: Enter the desired frequency output at startup. Modbus control only.

40019 – Max Frequency Output: Enter the desired maximum frequency output when in analog control modes.

40020 – Idle Frequency Output: Enter the desired Idle frequency output when in analog control modes.

40021 – Contact Closure Frequency: Enter the desired output frequency when CC is activated. Non-Isolated digital control.

40022 – Max Control %: Used in 0-5V, 0-10V, 4-20mA, and Pot control. It sets the analog control percentage point of where the Max Frequency output occurs.

40023 – Idle Control: The Idle control register is used in 0-5V, 0-10V, 4-20mA, and Pot control. It sets the Idle frequency control percentage. Refer to 40013.

40024 – Alarm Control: The alarm control register is used in 0-5V, 0-10V, 4-20mA, and Pot control. It sets the alarm control percentage. 0=Disabled. Refer to 40013.

40025 – Max Temperature: The max temperature register is used in Thermistor control. It sets the Temperature threshold for max frequency output. Refer to 40019 for setting Max Freq output value.

40026 – Idle Temperature: Used in thermistor control mode to set the temperature threshold for idle frequency. Refer to register 40020 for setting Idle Freq value.

40027 – Alarm Temperature: Used in thermistor control mode to set the temperature threshold for an alarm.

40028 – Baud Rate: Sets the Modbus communication Baud rate. Range from 2,400 – 500,000 (100 Baud Res). *Recovery: Setting SW2 for ID 0 will set Baud to 9600.

40029 – PWM Frequency: Sets the sine wave modulation frequency. Range from 2,000 – 20,000 Hz. Default = 16,000Hz

40030 – EEPROM Save: Setting this register to a 1 saves the control variables into EEPROM. EEPROM Save is also used to set variables to default.


Stratus II Variable Frequency Drive AC Motor Speed Control Manual Pages

Use the links below for addtional manual pages or for a complete manual or click on the Operation/Installation Manual PDF link above.