MOTOR COMPATIBILITY
For maximum motor life without
using a line filter, the use of an inverter duty motor is recommended.
Electrical Noise Emissions and filtering: Electrical
noise emissions (EMI) are highly dependent on load and
environment. For many applications no additional
filtering is required to meet EN55011/FCC class A
emissions standards. For applications requiring
additional filtering CRI recommends the following filters
or equivalents:
Controlling multiple motors: Multiple motors wired in
parallel can be controlled from one Stratus II as long as
maximum peak (startup) currents do not exceed 10
Amps.
Control Accuracy and Hysteresis: Control signal
accuracy is as follows:
Voltage ± 0.38VDC
Current ± 0.4mA
Temperature ± 1.5Cº
In alarm conditions, loss of signal and ON/OFF feature,
hysteresis is added to eliminate cycling. Hysteresis is as
follows:
Voltage ± 2%
Current ± 1.5%
Temperature 1-2Cº
RoHS compliance: Stratus II is RoHS (6/6) compliant |
Maximum Fan Current: Some motors draw higher
current at less than maximum voltage. Contact motor
manufacturer for details.
HiPot Testing: Stratus II is designed to withstand HiPot
testing to 1500Vrms, line input to analog input, motor
output to analog input.
Current Derating:
Specifications:
- Input Power: 115 & 230 VAC +/-10% 47-64 Hz
Single Phase, 5.7 Amps
- Output Power: 115 & 230 VAC +/-10% 0-400 Hz
Single Phase, 4.0 Amps
- Maximum peak (startup) current: 10 Amps
- Storage Temperature: -40°C to 125°C
- Operating Temperature: -20°C to 40°C (full load)
- Thermal shutdown at 100°C
- Relative Humidity: 95% non-condensing
- Weight (with cover): 1.8 lb (816 grams)
- Weight (no cover): 1.2 lb (544 grams)
|