| TachStrip
Fan
speed alarm |
|
SmartFan
TachStrip
is a modular fan speed alarm
that accepts tachometer (Hall
Effect) pulses from DC
or AC fans or blowers. TachStrip monitors these
pulses
and generates failure alarms if air mover speed
drops
below a preset trigger speed. TachStrip comprises
a
strip of 6 individual alarm units bused together.
The
web separating units can be cut to provide strips
to
|
handle
any quantity of fans.Each
unit monitors one
air mover and provides alarm outputs for that
air
mover. The bus distributes power to each unit
and ORs alarm signals from each unit to
provide
a single alarm output if any air mover should
fail.
Each alarm unit has three outputs used to drive
a logic circuit, LED, or piezo alarm. |
|
| For
Application and Design Information See: |
| |
|
| Features |
- Accepts
open collector or voltage source pulses from nearly
any DC
or AC fan or blower.
- 6
alarm unit strips are easily separated to monitor
any quantity
of fans.
- Distributes
power to DC air movers through same connector used
to sense pulses.
- Separate
alarm outputs are provided for each fan
- Alarm
channels are OR’d providing a single alarm if
any fan fails.
- Trigger
Speed is adjustable by jumper to 1500, 2500, or 4000
PPM.
- Permissible
power supply voltage is 5.0 VDC minimum to 25.0
VDC maximum.
|
Normally
Closed (NC) Alarm Output Closed above trigger speed and will sink
4 mA at 0.4 VDC or less.
Open below trigger speed and will accept up to
30
VDC. Referenced to fan negative terminal.
Applies nominal 12 mA to an LED
connected from NC to L.
Normally
Open (NO) Alarm Output Open above trigger speed and will accept
up to 30 VDC. Closed below trigger speed and will sink
4 mA at 0.4 VDC or less.
Referenced
to negative fan terminal. Applies nominal 12 mA to an
LED
connected from NO to L. Applies nominal power supply
voltage to piezo
alarm connected from NO to P.
ORd
(OR) Alarm Output ORd with all other alarm units in TachStrip.
Other characteristics identical to NO alarm output.
|
| Specifications |
| Part
Number |
Supply
Voltage Range |
Alarm
Units Per Strip |
| 015B125
015B625 |
5
to 25 VDC |
1
6 |
| H1091
|
Hardware
Pack |
Note: Maximum
operating temperature is 65°C
1per alarm unit.
| To
view installation and operation instructions: |
| |
|
|
|

CRI
Home | News & Info
| Technical Data
| Catalog | Contact
Us | Applications
| About
Control Resources | Site Map |
Control Resources Incorporated
11 Beaver Brook Road
Littleton MA, 01460 USA
Tel: 978-486-4160
Fax: 978-486-4772
email: sales@controlres.com
|